Faulty cable caused prolonged Canefield substation outage – GPL

November 23 2026
A defective 500mm cable with a short circuit to ground was identified as the critical fault behind the prolonged electricity outage that affected sections of East Berbice for nearly three days, Guyana Power and Light Inc. (GPL) has disclosed.
The outage began at approximately 8:14 p.m. on Thursday, November 19, when the T2 13.8 kV incomer at the Canefield Substation tripped, causing all circuits to lose power and locking out the 13.8 kV bus.
Shortly afterwards, a flash was reported from the B4T1 cubicle during attempts to restore the system, prompting GPL to dispatch a specialised technical team to investigate and carry out repairs.
According to the company, technicians arrived during the early hours of Friday, November 20, and began systematic checks of the substation equipment, including controlled switching, testing of potential transformers, inspecting the busbar system and repairing areas showing deterioration or electrical tracking.
Several equipment deficiencies were identified, including deteriorated potential transformers, condensation inside the SG2 switchgear cubicle, suspect insulation and components, and poor insulation-resistance readings.
The affected components were cleaned, repaired, re-insulated and tested, with some suspect parts replaced. However, repeated attempts to energise the system continued to trigger protective tripping.
Technicians subsequently isolated and tested different components in an effort to locate the fault. The ST2 auxiliary transformer was found to be damaged based on its insulation-resistance results and was disconnected. However, the system continued to trip when another attempt was made to energise the bus, indicating that the damaged transformer was not the only problem.
Troubleshooting continued overnight into Saturday, November 21, involving further dismantling, testing and reassembly of switchgear components. Specialist support was also brought in to assist with testing the busbar, grounding transformer, switches and associated equipment.
GPL said technicians also undertook extensive refurbishment of the substation’s SG2 panel, which was constructed in 1975, using available spare components.
A breakthrough came at approximately 3:30 p.m. on Saturday, when arcing was observed beneath metal covers over a recently installed 500mm² cable during another attempt to energise the system. The T2 transformer incomer protection relay also registered a trip, directing the investigation towards the cable.
Subsequent insulation-resistance tests confirmed that the cable’s B-phase was defective, with a short circuit to ground.
The technical team then tested the previously installed 400mm² incomer cable, which was found to be suitable for use. At approximately 6:00 p.m., work began to reconnect it to the 60 MVA transformer terminal and the transformer incomer cubicle of the 13.8 kV switchgear.
At 6:25 p.m. on Saturday, technicians successfully re-closed the bus tie, allowing electricity supply to be restored in phases.
Working alongside System Control, substation operatives energised feeders F1 and F4, restoring power from New Amsterdam to Mara along the eastern bank of the Berbice River. Feeder F3, which supplies customers between Canje and Williamsburg, was subsequently restored.
Following the restoration of the main electrical system, crews continued working to reinstate the substation’s auxiliary power supply.
Since the damaged ST2 auxiliary transformer had been removed from service, alternative transformers on site were tested and a replacement auxiliary supply installed. The work was completed at approximately 1:30 a.m. on Sunday, November 22.
GPL said the restoration exercise required extensive diagnostic testing because several equipment abnormalities were discovered, while repeated attempts to energise the system continued to result in protective tripping.
The company acknowledged the disruption caused to households, businesses and other customers in East Berbice and apologised for the prolonged outage.
It also thanked residents and businesses for their patience and understanding, while recognising the efforts of the technical personnel who worked continuously to identify the fault and restore electricity.
GPL said it would review the circumstances surrounding the outage and the equipment deficiencies identified during the restoration exercise, with the aim of strengthening infrastructure reliability and reducing the likelihood of similar prolonged disruptions.