Home›News›Faulty cable caused prolonged Canefield substation outage – GPL

Faulty cable caused prolonged Canefield substation outage – GPL

By Savitri Laikram
23 November 2026
130
0
Share:

November 23 2026

 

A defective 500mm cable with a short circuit to ground was identified as the critical fault behind the prolonged electricity outage that affected sections of East Berbice for nearly three days, Guyana Power and Light Inc. (GPL) has disclosed.

 

The outage began at approximately 8:14 p.m. on Thursday, November 19, when the T2 13.8 kV incomer at the Canefield Substation tripped, causing all circuits to lose power and locking out the 13.8 kV bus.

 

Shortly afterwards, a flash was reported from the B4T1 cubicle during attempts to restore the system, prompting GPL to dispatch a specialised technical team to investigate and carry out repairs.

 

According to the company, technicians arrived during the early hours of Friday, November 20, and began systematic checks of the substation equipment, including controlled switching, testing of potential transformers, inspecting the busbar system and repairing areas showing deterioration or electrical tracking.

 

Several equipment deficiencies were identified, including deteriorated potential transformers, condensation inside the SG2 switchgear cubicle, suspect insulation and components, and poor insulation-resistance readings.

 

The affected components were cleaned, repaired, re-insulated and tested, with some suspect parts replaced. However, repeated attempts to energise the system continued to trigger protective tripping.

 

Technicians subsequently isolated and tested different components in an effort to locate the fault. The ST2 auxiliary transformer was found to be damaged based on its insulation-resistance results and was disconnected. However, the system continued to trip when another attempt was made to energise the bus, indicating that the damaged transformer was not the only problem.

 

Troubleshooting continued overnight into Saturday, November 21, involving further dismantling, testing and reassembly of switchgear components. Specialist support was also brought in to assist with testing the busbar, grounding transformer, switches and associated equipment.

 

GPL said technicians also undertook extensive refurbishment of the substation’s SG2 panel, which was constructed in 1975, using available spare components.

 

A breakthrough came at approximately 3:30 p.m. on Saturday, when arcing was observed beneath metal covers over a recently installed 500mm² cable during another attempt to energise the system. The T2 transformer incomer protection relay also registered a trip, directing the investigation towards the cable.

 

Subsequent insulation-resistance tests confirmed that the cable’s B-phase was defective, with a short circuit to ground.

 

The technical team then tested the previously installed 400mm² incomer cable, which was found to be suitable for use. At approximately 6:00 p.m., work began to reconnect it to the 60 MVA transformer terminal and the transformer incomer cubicle of the 13.8 kV switchgear.

 

At 6:25 p.m. on Saturday, technicians successfully re-closed the bus tie, allowing electricity supply to be restored in phases.

 

Working alongside System Control, substation operatives energised feeders F1 and F4, restoring power from New Amsterdam to Mara along the eastern bank of the Berbice River. Feeder F3, which supplies customers between Canje and Williamsburg, was subsequently restored.

 

Following the restoration of the main electrical system, crews continued working to reinstate the substation’s auxiliary power supply.

 

Since the damaged ST2 auxiliary transformer had been removed from service, alternative transformers on site were tested and a replacement auxiliary supply installed. The work was completed at approximately 1:30 a.m. on Sunday, November 22.

 

GPL said the restoration exercise required extensive diagnostic testing because several equipment abnormalities were discovered, while repeated attempts to energise the system continued to result in protective tripping.

 

The company acknowledged the disruption caused to households, businesses and other customers in East Berbice and apologised for the prolonged outage.

 

It also thanked residents and businesses for their patience and understanding, while recognising the efforts of the technical personnel who worked continuously to identify the fault and restore electricity.

 

GPL said it would review the circumstances surrounding the outage and the equipment deficiencies identified during the restoration exercise, with the aim of strengthening infrastructure reliability and reducing the likelihood of similar prolonged disruptions.

 

 

Share on Facebook Share
Share on TwitterTweet
Share on Pinterest Share
Share on LinkedIn Share
Share on Digg Share
Previous Article

$948.9M dredge, workboat added to NDIA fleet

Next Article

$11B supplementary funding approved for GSA, NDIA ...

0
Shares
  • 0
  • +
  • 0
  • 0
  • 0
  • 0

Related articles More from author

  • Businesswoman's vehicle torched
    Crime / Security

    Businesswoman’s vehicle torched

    15 February 2022
    By Leroy Smith
  • News

    Police arrests 16 year-old for shooting death of boy

    17 March 2021
    By Leroy Smith
  • News

    Cops question girl over alleged threats to torch Annai dorms.

    3 June 2023
    By Savitri Laikram
  • Crime / SecurityInternationalNewsRegionalTravel

    Mojtaba Khamenei becomes Iran’s Supreme Leader

    9 March 2026
    By Savitri Laikram
  • MANGROVE DESTRUCTION: Min. Bharat hopes there is no recurrence
    Arts & EntertainmentCommunity ReportNews

    MANGROVE DESTRUCTION: Min. Bharat hopes there is no recurrence

    17 May 2021
    By Leroy Smith
  • Crime / SecurityNews

    Bloodshed on the cricket pitch: Accused walks free

    1 April 2026
    By Savitri Laikram

You may interested

  • News

    UNAIDS to Discuss Deeper Cooperation in Public Health in Guyana and Suriname

  • News

    “Sunshine” jailed for 4 years, fined $16M for attempting to smuggle cocaine to the USA

  • Woman takes her life after checking into short-time hotel
    Crime / Security

    Woman takes her life after checking into short-time hotel

Timeline

  • 24 November 2026

    ‘Dream Realised’ brings land and building support to Region Six

  • 24 November 2026

    Two killed in separate road accidents along Silver Hill, Essequibo

  • 23 November 2026

    “Everybody screaming” – Engineer relives Barima’s final minutes

  • 23 November 2026

    Special Branch head draws blank on dealings with two ministers

  • 23 November 2026

    Three remanded on terrorism charges following attempted arson on Strathspey school

Latest Comments

  • Waitress/ daughter murdered by insecure Cuban National after visiting her brother - The Big Smith News ...
    on
    27 December 2020
    […] Tara Krishanran and her 11-year-old daughter Larissa Singh.  BIG Smith News Watch on Boxing Night ...

    BREAKING NEWS: Cuban National murders girlfriend and 11-Y-O child

  • Charges for constable in deadly Whim crash - The Big Smith News Watch
    on
    14 December 2020
    […] Constable Simion Alder, who was reportedly under the influence of alcohol when he crashed the motorcar he ...

    GDF rank among three killed in Whim smashup

  • Charges for drunk constable in deadly Whim - The Big Smith News Watch
    on
    14 December 2020
    […] Constable Simion Alder, who was reportedly under the influence of alcohol when he crashed the ...

    GDF rank among three killed in Whim smashup

  • Satchi
    on
    16 May 2019
    One gets terrified at Guyana Airport ,when the immigration officer takes my passport and walk away ...

    Immigration Officer found with 20 Passports at his home

  • Alexis Ward
    on
    16 May 2019
    Good job Mr Smith.

    Man escapes police custody hours before court appearance

Find us on Facebook

About US

logo

BIG Smith News Watch was established in 2015 and is recognized by the Guyana press Association as a legitimate media outlet in Guyana. Our operation focuses more community, human interest and developmental issues. We also do focus on matters of crime, security, business, politics and current affairs. The entity is headed by Leroy Smith, a practicing journalist with experience in news gathering, reporting and coverage spanning seventeen years. Mr. Smith joined the media 2005 and worked at several media housing before launching BIG Smith News Watch in 2015.

  • +592-705-8780
  • bigsmithnewswatch35@gmail.com
  • Popular Posts

  • Lance Corporal dies days after fight with police sergeant

    By Leroy Smith
    8 May 2019
  • Nonummy suspendisse hendrerit ultrices

    By DesignUTD
    26 August 2015
  • 21 Year Old mechanic busted with cocaine pellets in hotel room

    By Leroy Smith
    27 April 2019
  • Bandit shows up to robbery with ‘one bullet’; shot dead by security guard

    By Leroy Smith
    30 April 2019

Follow us

© Copyright www.bigsmithnewswatch.news. All rights reserved.